| Heat Flow Meter Range | 0 to 100kW/m² |
| Heat Flow Meter Accuracy | ±3% |
| Heat Flow Meter Repeatability | ±0.5% |
| Sample Weighing Range | 0 to 2000 g |
| Sample Weighing Accuracy | ±0.1 g |
| Oxygen Analyzer Range | 0 to 25% |
| Oxygen Analyzer Response Time | Less than 12s |
| Oxygen Analyzer Output Noise | Less than 50 ppm |
| Infrared Heater | 6 × 500W quartz lamps |
| Ceramic Tube Igniter | 4-hole |
| Spark Ignition | 10kV |
| CO₂ Analyzer Range | 0 to 10% |
| CO₂ Analyzer Accuracy | ±0.01% |
| Exhaust Fan Flow Rate | Adjustable 0 to 50g/s |
| Exhaust Fan Flow Rate Accuracy | 0.1g/s |
| Cold Trap Temperature Range | 0 to 8°C |
| Diaphragm Pump Flow Rate | 3L/min |
| Detector Accuracy | ±5% |
| Detector Accuracy Transmittance | Less than 1% |
| Absolute Pass Rate | Less than 1% |
| Power Supply | AC380V, 50HZ |
| Dimension | 2400 × 800 × 2000 mm |
| Packaging Dimension | 2600 × 1000 × 2200 mm |
| Net Weight | 500 Kg |
| Gross Weight | 530 Kg |
User-friendly interface
Automatic ignition
Stainless steel cold sink
Durable
Auto-recording
Graphical output.
Flame propagation calorimeter LFPC-A10 help assess material flammability, flame spread speed, fire patterns, and hazards. They provide essential data for building design, product safety, and material development.
Download catalog for
Flame Propagation Calorimeter LFPC-A10 Catalog
The Labtron Flame Propagation Calorimeter is designed to measure the heat release rate, flame spread, and combustion characteristics of materials. It helps analyze ignition time, peak heat release, and total energy output under controlled conditions. This data is crucial for fire safety research, material testing, and regulatory compliance assessments.
The calorimeter uses a PID control system for precise temperature regulation. It is equipped with thermocouples that continuously monitor the radiation cone and exhaust temperature. This ensures stable heating conditions and accurate measurement of material combustion properties.
The oxygen analyzer in the Labtron Flame Propagation Calorimeter measures oxygen concentration from 0% to 25%. Additionally, the system includes gas analyzers that can detect CO and CO? levels, ensuring comprehensive monitoring of combustion byproducts.
The system automatically saves sample numbers, test parameters, and temperature curves for each experiment. The LabVIEW-based software allows users to access, analyze, and export data easily. This helps in reviewing test results and maintaining records for future reference.
The calorimeter is widely used in industries such as fire safety, building materials, aerospace, textiles, and polymers. It helps manufacturers and researchers evaluate the flammability of materials, improve fire-resistant designs, and meet safety standards required for various applications.
Post your question?
Our experts are here to help!
Labtron Equipment Ltd., Quatro House, Lyon Way, Camberley, Surrey GU16 7ER United Kingdom
Email: info@labtron.com Whatsapp: +44 73 4441 2688 Phone: +44 2080 043608