Wall Mounted Gas Detector LAGD-A10 includes one control panel with H2 detector, HCN detector, NH3 detector, and O2 detector. The panel supports 1 to 4 channels of 4 to 20 mA signal acquisition and is compatible with various gas detectors. It allows gas-type switching between oxygen and non-oxygen gases. Also, it supports customization of high and low alarm thresholds and measurement range settings. Our detector plays a central role in managing devices such as solenoid valves, exhaust fans, motors, and water pumps.
| Gases Detected | Hydrogen (H₂), Hydrogen cyanide (HCN), Ammonia (NH₃), Oxygen (O₂) |
| Detection Principle | Electrochemistry (HCN, NH₃, O₂), Catalytic (H₂) |
| Precision | ≤ ±2% FS |
| Measuring Range | H₂: 0 to 100% LEL, HCN: 0 to 100 ppm, NH₃: 0 to 100 ppm |
| Response Time | T90 < 60s |
| Working Temperature | Catalytic Sensor: -40°C to 70°C; Electrochemistry Sensor: -20°C to 50°C |
| Working Pressure | 91 kPa to 111 kPa |
| Working Humidity | 10% to 95% RH |
| Working Temperature (Controller) | -10°C to +50°C |
| Working Humidity (Controller) | ≤95% RH (non-condensing) |
| Repeatability | ±2% FS |
| Explosion-Proof Grade | IECEx: Ex db IIC T6 Gb, Ex db ia IIC T6 Gb, ATEX: Ex db IIC T6 Gb, Ex db ia IIC T6 Gb |
| Communication Mode | Standard: 1 set of 4–20 mA (3 wires), RS485, 2 sets of relay (30V, 2A) |
| Display | 1.21-inch OLED, Resolution: 160 × 64 |
| Power Consumption | Toxic gas < 2.5 W |
| Protection Grade | IP66 / IP68 |
| Wireless Option | LORA, 4G |
| Working Voltage | 12 to30 VDC |
| Housing Material | Die-cast aluminum |
| Electrical Interface | NPT3/4 |
| Data Storage | 1000 event sets per channel |
| Input Channel | 4 to 20 mA; available in 1-channel, 2-channel, and 4-channel options |
| Installation Method (Controller) | Wall-mounted |
| Concentration Display | 4 digits (0.001 to 9999) |
| Communication Mode (Controller) | 4 to 20 mA |
| Inspection | 200 ms |
| Power Supply | AC 100 to 220 V, 50/60 Hz ,DC 24 V, 0.25 A per channel |
| Dimensions | 178 × 129 × 90 mm |
| Controller Dimensions | 73.7 × 192.5 × 83.7 mm |
| Controller weight | ≤1.7 kg |
| Weight | 1.4 kg |
Built-in sound and light alarm system
24-hour continuous online detection
One-person calibration via calibration cap
Remote control using infrared or magnetic wand
Reverse wiring protection
Fast and accurate sensor response
Our Wall Mounted Gas Detector LAGD-A10 is used for continuous monitoring of toxic gases, oxygen, and flammable gases. It can be employed in industrial settings such as chemical plants, refineries, and manufacturing facilities.
Labtron Equipment Ltd., Quatro House, Lyon Way, Camberley, Surrey GU16 7ER United Kingdom
Email: info@labtron.com Whatsapp: +44 73 4441 2688 Phone: +44 2080 043608